Ultraviolet Water Disinfection Systems
In many situations, the most common problem affecting ultraviolet (UV) water disinfection is the fouling of the quartz sleeve which surrounds the UV lamp. The rate of sleeve fouling is influenced by water temperature, water flow, and water quality – specifically the concentrations of calcium, magnesium, and iron in the water, which are the most common constituents that lead to sleeve fouling.
Under no-flow conditions through the UV chamber, the water temperature increases, which causes an accelerated rate of calcium, magnesium, and iron deposits precipitating onto the quartz sleeve. This decreases the level of UV transmittance and eventually requires the sleeve to be cleaned.
While actual water usage may vary significantly in a 24-hour period, conditions of no water flow typically account for as much as 60% of the day. During this time, the UV lamp heats the water, resulting in water temperatures as high as 55˚C (131˚F) in the chamber and significantly increasing the rate of sleeve fouling.
VIQUA’s new LightWise technology allows the controller to reduce lamp power during periods of no water flow, leading to estimated energy savings of 30%. By adjusting the lamp power, water temperature is maintained below 40˚C (104˚F), and the rate of sleeve fouling is consequently reduced by as much as 60%. This can more than double the amount of time between sleeve cleaning cycles.
FEATURES OF VIQUA UV WATER DISINFECTION SYSTEMS
-
LightWise Technology allows the controller to reduce lamp power during
periods of no water flow. By adjusting the lamp power, water temperature
is maintained below 40˚C (104˚F), the rate of sleeve fouling is
consequently reduced by as much as 60%, resulting in estimated energy
savings of 30%. -
The CoolTouch Fan significantly reduces water temperature and does not
waste any water. -
For the sleeve bolts a quartertwist to the positive stop and you’re
done. No tools, no risk of over-tightening. - Like a standard plug – no more grounding wires!
-
The optional plug-and-play solenoid valve stops water flow in the event
that water treatment is compromised. - Assembly is simplified by the use of an integral flow restrictor.
- Flexibility to connect to either 1¼” MNPT or 1” FNPT.
- New and improved sensor ensures safe UV levels are maintained.
-
Our revolutionary amalgam lamps reduce maintenance requirements by
lasting up to 2 years. - Intuitive Interface – a picture is worth a thousand words.
-
The VIQUA systems use a revolutionary lamp with twice the output of
current high-output lamps, giving you compact singlelamp systems that
are half the size of their predecessors. -
With plug-and-play colour coded connections, it’s as easy as “connect
the dots.” -
The optional COMMcenter displays UV dose and can monitor up to 9 UV
systems – that’s up to 270 gpm! - Flow sensor monitors flow to provide real time UV dose.
- Lower maintenance (Up to 60% less maintenance).
-
Decrease conditions that contribute to fouling and corresponding
maintenance. - Increase time period between required maintenance.
- Eliminate the need for a complicated mechanical sleeve cleaning system.
-
Estimated energy savings of 30% (Typical two unit [PRO20] installation
uses 2800 kW/yr). -
Water temperature is maintained below 40˚Celsius (104˚F) in noflow
conditions. - Eliminates the need for hot water purging in no-flow conditions.
SPECIFICATIONS
|
|
|
||
| MODELS | PRO10 | PRO20 | PRO30 | |
| FLOW RATES (@ 70% UVT) | ||||
| NSF/EPA (40 mJ/cm2) | 10 GPM (38 lpm) (2.3 m3/hr) | 20 GPM (76 lpm) (4.5 m3/hr) | 30 GPM (113 lpm) (6.8 m3/hr) | |
| DIMENSIONS | ||||
| Chamber | 22” x 4” (54 cm x 10 cm) | 31” x 4” (78 cm x 10 cm) | 41” x 4” (103 cm x 10 cm) | |
| Controller | 13” X 6.5” x 4.5” (33 cm x 16.5 cm x 11.5 cm) | 13” X 6.5” x 4.5” (33 cm x 16.5 cm x 11.5 cm) | 13” X 6.5” x 4.5” (33 cm x 16.5 cm x 11.5 cm) | |
| Inlet/Outlet Port Size | 1 1/4” MNPT / 1” FNPT COMBO | 1 1/4” MNPT / 1” FNPT COMBO | 1 1/4” MNPT / 1” FNPT COMBO | |
| Shipping Weight | 25 lbs (11.3 kg) | 28 lbs (12.7 kg) | 31 lbs (14 kg) | |
| ELECTRICAL | ||||
| Voltage | 100-240V / 50/60 Hz | 100-240V / 50/60 Hz | 100-240V / 50/60 Hz | |
| Power Consumption | 120 W | 160 W | 230 W | |
| Maximum Operating Pressure | 125 psi (8.62 bar) | 125 psi (8.62 bar) | 125 psi (8.62 bar) | |
| Influent Water Temperature | 2-40°C (36-104°F) | 2-40°C (36-104°F) | 2-40°C (36-104°F) | |
| FEATURES | ||||
| Visual “Power On” | YES | YES | YES | |
| Chamber Material | 316L SS | 316L SS | 316L SS | |
| Visual Lamp Life Remaining | YES | YES | YES | |
| Audible Lamp Failure | YES | YES | YES | |
| Audible Lamp Replacement Reminder | YES | YES | YES | |
| UV Sensor | YES | YES | YES | |
| Sensor Reading Output (4-20mA) | Optional | Optional | Optional | |
| Flow Meter | YES | YES | YES | |
| Cool Touch Fan | YES | YES | YES | |
| Optional Solenoid Valve | YES (650627) | YES (650627) | YES (650627) | |
REPLACEMENT PARTS
| 602854 – UV lamp for PRO10 | 602976 – quartz sleeve for PRO30 |
| 602855 – UV lamp for PRO20 | 650709-003 – power supply for PRO10 |
| 602856 – UV lamp for PRO30 | 650709-006 – power supply for PRO20 |
| 602974 – quartz sleeve for PRO10 | 650709-009 – power supply for PRO30 |
| 602975 – quartz sleeve for PRO20 | 650580 – sensor for PRO10, PRO20 & PRO30 |
WATER QUALITY PARAMETERS
| Hardness | Iron | Tannins |
|---|---|---|
| < 7 grains (120 mg/L) | < 0.3 mg/L | < 0.1 mg/L |
THE RIGHT SOLUTION FOR YOU
Contact us today for more information about our products and services.